SSVC status
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.
Active exploitation of CVE-2022-33174 has not been confirmed. The EPSS score is 81.7%, indicating the estimated probability of exploitation in the next 30 days.
CVE-2022-33174 has a CVSS v3 base score of 7.5 (HIGH severity).
Use isMalicious to check if any of your IPs or domains are associated with this vulnerability's IOCs.
Ranked by exploit probability (EPSS).