Skip to main content
No exploitation reportedFix available

CVE-2021-32960

No exploitation reported by the sources we read.

  • Published2022-04-01
  • WeaknessCWE-693 · CWE-863

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.

Timeline

dates in UTC
  1. 2022-04-0123:15CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2021-32960?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2021-32960?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Rockwellautomation factorytalk services platform
BranchAffectedFixed in
6.11≤ 6.11.00no fix published

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-21-161-01 CISA1 known affected

    Rockwell Automation FactoryTalk Services Platform

    FactoryTalk Services Platform: v6.11 and earlier if FactoryTalk Security is enabled and deployed

Full record on NVD

Fix

  1. Vendor fix CISA ICSA-21-161-01 · 1 productRockwell Automation encourages those using the affected software to update to FactoryTalk Services Platform v6.20 or later to address the associated risk.
  2. Mitigation from the vendor CISA ICSA-21-161-01 · 1 productWhen possible, do not utilize remote desktop connections.
  3. Mitigation from the vendor CISA ICSA-21-161-01 · 1 productUse Microsoft Event Logger or similar event logging application to monitor atypical remote desktop connections and disconnections. Information on Setting up Windows Event Logs is available at Knowledgebase Article QA5965
  4. Mitigation from the vendor CISA ICSA-21-161-01 · 1 productRun all software as User, not as an Administrator, to minimize the impact of malicious code on the infected system.
  5. Mitigation from the vendor CISA ICSA-21-161-01 · 1 productEnsure the least-privilege user principle is followed, and user/service account access to shared resources (such as a database) is only granted with a minimum number of rights as needed.
  6. Mitigation from the vendor CISA ICSA-21-161-01 · 1 productWhen remote access is required, use secure methods, such as virtual private networks (VPNs), recognizing that VPNs may have vulnerabilities and should be updated to the most current version available. Also recognize VPN is only as secure as the connected devices.

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CISA-ADPSSVC decisionnone2025-04-17
  • OpenCVESSVC decisionnone—
  • CNACVSS 3.18.5read 2026-10-23
  • NVDCVSS 3.18.8read 2026-10-23
  • NVDCVSS 2.06read 2026-10-23
  • CISA-ADPweakness (CWE)CWE-6932025-04-17
  • NVDweakness (CWE)CWE-863read 2026-10-23
  • FIRST EPSSEPSS score2.4 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H
Published
2022-04-01
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2021-32960?

Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.

Is CVE-2021-32960 actively exploited?

Active exploitation of CVE-2021-32960 has not been confirmed. Its EPSS score was 2.4% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2021-32960?

CVE-2021-32960 has a CVSS v3 base score of 8.8 (HIGH severity), with vector string CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H.

Running Rockwell Automation FactoryTalk? Hear about its next vulnerability

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month