Skip to main content
No exploitation reportedFix available

CVE-2021-22805

No exploitation reported by the sources we read.

  • Published2022-02-11
  • WeaknessCWE-306

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)

Timeline

dates in UTC
  1. 2022-02-1118:15CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 21:37 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2021-22805?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2021-22805?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Schneider-electric interactive graphical scada system data collector
BranchAffectedFixed in
15.0≤ 15.0.0.21243no fix published

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-21-285-03 CISA1 known affected

    Schneider Electric IGSS

    IGSS Data Collector (dc.exe): v15.0.0.21243 and prior

Full record on NVD

Fix

  1. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productSchneider Electric recommends users update to Version 15.0.0.21244 of the IGSS DC module. Please note, dc.exe includes fixes for these vulnerabilities and is available for download through IGSS Master > Update IGSS Software or at the IGSS update link.
  2. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productUsers should employ appropriate patching methodologies. Schneider Electric strongly recommends the use of backups as well as an evaluation of the impact of these patches in a test and development environment or an offline infrastructure. Contact Schneider Electric's Customer Care Center if you need…
  3. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productIf users choose not to apply the remediation provided above, they should immediately apply the following mitigations to reduce the risk of exploit:
  4. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productOnly accept incoming connections from machines, which names have been added as a station in the IGSS System Configuration module by setting the registry key called “MatchWinName” to 1 under: “HKEY_CURRENT_USER\SOFTWARE\SchneiderElectric\IGSS32\V15.00.00\DC_HKLM\”
  5. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productFollow the general security recommendation below and verify devices are isolated on a private network and firewalls are configured with strict boundaries for devices that require remote access.
  6. Mitigation from the vendor CISA ICSA-21-285-03 · 1 productFor more information see Schneider Electric's security notification: SEVD-2021-285-03

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • NVDCVSS 3.19.1read 2026-10-23
  • NVDCVSS 2.05read 2026-10-23
  • CNAweakness (CWE)CWE-306read 2026-10-23
  • FIRST EPSSEPSS score0.9 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H
Published
2022-02-11
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2021-22805?

A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause deletion of arbitrary files in the context of the user running IGSS due to lack of validation of network messages. Affected Product: Interactive Graphical SCADA System Data Collector (dc.exe) (V15.0.0.21243 and prior)

Is CVE-2021-22805 actively exploited?

Active exploitation of CVE-2021-22805 has not been confirmed. Its EPSS score was 0.9% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2021-22805?

CVE-2021-22805 has a CVSS v3 base score of 9.1 (CRITICAL severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H.

Hear about the next vulnerability in your software

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month