Description

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.

Timeline

dates in UTC
  1. 2021-02-0918:15CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2020-28388?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2020-28388?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Siemens capital vstar
BranchAffectedFixed in
—all versionsno fix published
Siemens nucleus net
BranchAffectedFixed in
5.2< 5.25.2
Siemens nucleus readystartversion to verify
BranchAffectedFixed in
2012.12< 2012.122012.12

2 more products in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-22-349-16 CISA6 known affected

    Siemens APOGEE and TALON

    APOGEE PXC Compact (BACnet) · APOGEE PXC Compact (P2 Ethernet) · APOGEE PXC Modular (BACnet) · +3 more

  • ICSA-21-068-08 CISA1 known affected

    Siemens Energy PLUSCONTROL 1st Gen

    Siemens PLUSCONTROL 1st Gen: All versions

Full record on NVD

Fix

  1. Vendor fix CISA ICSA-22-349-16 · 2 productsUpdate to V2.8.20 or later version
  2. Vendor fix CISA ICSA-22-349-16 · 4 productsUpdate to V3.5.5 or later version
  3. Mitigation from the vendor CISA ICSA-21-068-08 · 1 productPLUSCONTROL devices are typically located in a separate LAN segment of energy transmission solutions, where an attacker could use this vulnerability to disrupt SER messages or Trace functionalities. Therefore, review the status of the defense in depth recommendations that apply to your specific dep…

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CISA-ADPSSVC decisionnone2026-06-02
  • OpenCVESSVC decisionnone—
  • CNACVSS 3.16.5read 2026-10-23
  • NVDCVSS 3.15.3read 2026-10-23
  • NVDCVSS 2.05read 2026-10-23
  • CNAweakness (CWE)CWE-342read 2026-10-23
  • FIRST EPSSEPSS score1.4 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N
Published
2021-02-09
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2020-28388?

A vulnerability has been identified in APOGEE PXC Compact (BACnet) (All versions < V3.5.5), APOGEE PXC Compact (P2 Ethernet) (All versions < V2.8.20), APOGEE PXC Modular (BACnet) (All versions < V3.5.5), APOGEE PXC Modular (P2 Ethernet) (All versions < V2.8.20), Nucleus NET (All versions < V5.2), Nucleus ReadyStart V3 (All versions < V2012.12), Nucleus Source Code (All versions), PLUSCONTROL 1st Gen (All versions), TALON TC Compact (BACnet) (All versions < V3.5.5), TALON TC Modular (BACnet) (All versions < V3.5.5). Initial Sequence Numbers (ISNs) for TCP connections are derived from an insufficiently random source. As a result, the ISN of current and future TCP connections could be predictable. An attacker could hijack existing sessions or spoof future ones.

Is CVE-2020-28388 actively exploited?

Active exploitation of CVE-2020-28388 has not been confirmed. Its EPSS score was 1.4% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2020-28388?

CVE-2020-28388 has a CVSS v3 base score of 5.3 (MEDIUM severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:N.