Skip to main content
No exploitation reportedFix available

CVE-2024-31484

No exploitation reported by the sources we read.

  • Published2024-05-14
  • Fixed in16.41
  • WeaknessCWE-170

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition.

Timeline

dates in UTC
  1. 2024-05-1416:16CVE publishedNVD

Versions per branch

CISA-ADP
Siemens cpc80 central processing\/communication
BranchAffectedFixed in
16.41< 16.4116.41
Siemens cpci85 central processing\/communication
BranchAffectedFixed in
5.30< 5.305.30

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Products declared by the CNA6 products

As siemens, the CNA that assigned this CVE, declared them in the CVE record; versions as written.

  • Siemens CPC80 Central Processing/Communicationother versions: unknown
    Affected
    • < V16.41fixed in V16.41custom
  • Siemens CPCI85 Central Processing/Communicationother versions: unknown
    Affected
    • < V5.30fixed in V5.30custom
  • Siemens CPCX26 Central Processing/Communicationother versions: unknown
    Affected
    • < V06.02fixed in V06.02custom
  • Siemens ETA4 Ethernet Interface IEC60870-5-104other versions: unknown
    Affected
    • < V10.46fixed in V10.46custom
  • Siemens ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2other versions: unknown
    Affected
    • < V03.27fixed in V03.27custom
  • Siemens PCCX26 Ax 1703 PE, Contr, Communication Elementother versions: unknown
    Affected
    • < V06.05fixed in V06.05custom

Source: the CNA record (CVE Program), © The MITRE Corporation,CVE Terms of UseCVE recordupdated 2024-06-11

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-24-165-09 CISA4 known affected

    Siemens SICAM AK3/BC/TM

    CPCX26 Central Processing/Communication · ETA4 Ethernet Interface IEC60870-5-104 · ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 · +1 more

  • SSA-620338 Siemens ProductCERT4 known affected

    SSA-620338: Buffer Overflow Vulnerability in SICAM AK3 / BC / TM

    CPCX26 Central Processing/Communication · ETA4 Ethernet Interface IEC60870-5-104 · ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 · +1 more

  • ICSA-24-137-02 CISA2 known affected

    Siemens SICAM Products

    CPC80 Central Processing/Communication · CPCI85 Central Processing/Communication

  • SSA-871704 Siemens ProductCERT2 known affected

    SSA-871704: Multiple Vulnerabilities in SICAM Products

    CPC80 Central Processing/Communication · CPCI85 Central Processing/Communication

Full record on NVD

Fix

  1. Update Siemens cpc80 central processing\/communication to 16.41
  2. Vendor fix Siemens ProductCERT SSA-620338 · 1 productUpdate to V06.02 or later version. The firmware CPCX26 V06.02 is present within “SICAM RTUs AK3 Package” V06.02
  3. Vendor fix Siemens ProductCERT SSA-620338 · 1 productUpdate to V06.05 or later version The firmware PCCX26 V06.05 is present within “SICAM RTUs AK3 Package” V06.02
  4. Vendor fix Siemens ProductCERT SSA-620338 · 1 productUpdate to V10.46 or later version The firmware ETA4 V10.46 is present within “SICAM RTUs AK3 Package” V06.02
  5. Vendor fix Siemens ProductCERT SSA-620338 · 1 productUpdate to V03.27 or later version The firmware ETA5 V03.27 is present within “SICAM RTUs AK3 Package” V06.02
  6. Vendor fix CISA ICSA-24-165-09 · 1 productUpdate to V06.02 or later version. The firmware CPCX26 V06.02 is present within “SICAM RTUs AK3 Package” V06.02
  7. Vendor fix CISA ICSA-24-165-09 · 1 productUpdate to V06.05 or later version The firmware PCCX26 V06.05 is present within “SICAM RTUs AK3 Package” V06.02

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof of concept
Metasploit modules
none listed
Metasploit Framework

Sources

  • NVDCVE recordread 2026-10-23
  • CISA-ADPSSVC decisionnone2024-05-28
  • CNACVSS 4.07.3known since 2026-10-23
  • CNACVSS 3.17.8known since 2026-10-23
  • CNAweakness (CWE)CWE-170known since 2026-10-23
  • FIRST EPSSEPSS score0.5 %2026-11-08
  • GitHub Advisoriesadvisory—

Identifiers

Technical details

CVSS v3 Vector
CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
CVSS 4.0 vector
CVSS:4.0/AV:L/AC:H/AT:N/PR:N/UI:P/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Published
2024-05-14
Last Modified
2026-06-17
NVD status
Deferred
GitHub Advisory
GHSA-42vc-vfqh-cr2x

Frequently asked questions

What is CVE-2024-31484?

A vulnerability has been identified in CPC80 Central Processing/Communication (All versions < V16.41), CPCI85 Central Processing/Communication (All versions < V5.30), CPCX26 Central Processing/Communication (All versions < V06.02), ETA4 Ethernet Interface IEC60870-5-104 (All versions < V10.46), ETA5 Ethernet Int. 1x100TX IEC61850 Ed.2 (All versions < V03.27), PCCX26 Ax 1703 PE, Contr, Communication Element (All versions < V06.05). The affected devices contain an improper null termination vulnerability while parsing a specific HTTP header. This could allow an attacker to execute code in the context of the current process or lead to denial of service condition.

Is CVE-2024-31484 actively exploited?

Active exploitation of CVE-2024-31484 has not been confirmed. Its EPSS score was 0.5% on 2026-11-08, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2024-31484?

CVE-2024-31484 has a CVSS v3 base score of 7.8 (HIGH severity), with vector string CVSS:3.1/AV:L/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H.