Skip to main content
ExploitedIn CISA KEVFix available

CVE-2023-6448

Exploitation confirmed. First attested on 2023-12-06 by CISA-ADP, CISA KEV, GCVE · kevintel.

  • Published2023-12-05
  • Fixed in12.38
  • WeaknessCWE-1188 · CWE-798

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

Unitronics VisiLogic before version 9.9.00, used in Vision and Samba PLCs and HMIs, uses a default administrative password. An unauthenticated attacker with network access can take administrative control of a vulnerable system.

Timeline

dates in UTC
  1. 2023-12-0518:15CVE publishedNVD
  2. 2023-12-0614:07Exploitation first reportedCISA-ADP
  3. 2023-12-0614:07SSVC exploitation set to activeCISA-ADP
  4. 2023-12-11Added to the CISA KEV catalogCISA KEV
  5. 2023-12-11Listed as exploited by GCVEGCVE

Versions per branch

NVD
Unitronics samba 3.5 firmwareversion to verify
BranchAffectedFixed in
12.38< 12.3812.38
Unitronics samba 4.3 firmwareversion to verify
BranchAffectedFixed in
12.38< 12.3812.38
Unitronics samba 7 firmwareversion to verify
BranchAffectedFixed in
12.38< 12.3812.38

14 more products in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Products declared by the CNA1 product

As cisa-cg, the CNA that assigned this CVE, declared them in the CVE record; versions as written.

  • Unitronics VisiLogicother versions: unknown
    Affected
    • < 9.9.00fixed in 9.9.00custom

Source: the CNA record (CVE Program), © The MITRE Corporation,CVE Terms of UseCVE recordupdated 2023-12-19

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-23-348-15 CISA2 known affected

    Unitronics Vision and Samba Series (Update A)

    Unitronics VisiLogic: <9.9.00 · Unitronics OS: <12.38

Full record on NVD

Fix

  1. Update Unitronics samba 3.5 firmware to 12.38
  2. CISA’s required action: Apply mitigations per vendor instructions or discontinue use of the product if mitigations are unavailable.due 2023-12-18
  3. Vendor fix CISA ICSA-23-348-15 · 1 productUnitronics has patched this vulnerability in VisiLogic version 9.9.00 and recommends all users update to the latest version. Please see Unitronics' update log for more information.
  4. Mitigation from the vendor CISA ICSA-23-348-15 · 2 productsFor users who cannot update to the latest version, CISA urges organizations to:
  5. Mitigation from the vendor CISA ICSA-23-348-15 · 2 productsChange all default passwords on PLCs and HMIs and use a strong password. Ensure the Unitronics PLC default password "1111" is not in use.
  6. Mitigation from the vendor CISA ICSA-23-348-15 · 2 productsSet a password on PCOM-enabled sockets.
  7. Mitigation from the vendor CISA ICSA-23-348-15 · 2 productsControl remote enabled PCOM operations using SDW10 roles.
  8. Mitigation from the vendor CISA ICSA-23-348-15 · 2 productsDisconnect the PLC from the open internet. If remote access is necessary, control network access to the PLC.

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof of concept
Metasploit modules
none listed
Metasploit Framework

CISA Known Exploited Vulnerability

Date Added
2023-12-11
Patch Due Date
2023-12-18
Ransomware Use
Unknown
Required Action
Apply mitigations per vendor instructions or discontinue use of the product if mitigations are unavailable.

Sources

  • CISA KEVKEV entry2023-12-11
  • ENISA EUVDexploitation2023-12-112023-12-11
  • GCVEexploitation2023-12-11
  • CISA-ADPSSVC decisionactive2023-12-06
  • CNACVSS 3.19.8known since 2026-10-23
  • NVDCVSS 3.19.8read 2026-10-23
  • CNAweakness (CWE)CWE-1188known since 2026-10-23
  • NVDweakness (CWE)CWE-798read 2026-10-23
  • FIRST EPSSEPSS score2.1 %2026-11-19
  • GitHub Advisoriesadvisory—

Identifiers

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Published
2023-12-05
Last Modified
2026-06-17
NVD status
Analyzed
GitHub Advisory
GHSA-3r8p-3x67-72v8

Frequently asked questions

What is CVE-2023-6448?

Unitronics VisiLogic before version 9.9.00, used in Vision and Samba PLCs and HMIs, uses a default administrative password. An unauthenticated attacker with network access can take administrative control of a vulnerable system.

Is CVE-2023-6448 actively exploited?

Yes. CVE-2023-6448 is on the CISA Known Exploited Vulnerabilities (KEV) catalog, meaning it has been confirmed as actively exploited in the wild. CISA requires federal agencies to patch by 2023-12-18.

What is the CVSS score for CVE-2023-6448?

CVE-2023-6448 has a CVSS v3 base score of 9.8 (Critical severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.

Hear about the next vulnerability in your software

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month

Sources for this record