Skip to main content
No exploitation reported

CVE-2022-3752

No exploitation reported by the sources we read.

  • Published2022-12-19
  • WeaknessCWE-20

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.

Timeline

dates in UTC
  1. 2022-12-1923:15CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2022-3752?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2022-3752?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Rockwellautomation compact guardlogix 5380 firmwareversion to verify
BranchAffectedFixed in
31.11+≥ 31.011no fix published
Rockwellautomation compactlogix 5380 firmwareversion to verify
BranchAffectedFixed in
31.11+≥ 31.011no fix published
Rockwellautomation compactlogix 5480 firmwareversion to verify
BranchAffectedFixed in
32.11+≥ 32.011no fix published

2 more products in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-22-342-03 CISA5 known affected

    Rockwell Automation Logix controllers

    CompactLogix, Compact GuardLogix, ControlLogix, and GuardLogix controllers - CompactLogix 5380 controllers: firmware version 31.011 and later · CompactLogix, Compact GuardLogix, ControlLogix, and GuardLogix controllers - Compact GuardLogix 5380 controllers: firmware version 31.011 and later · CompactLogix, Compact GuardLogix, ControlLogix, and GuardLogix controllers - CompactLogix 5480 controllers: firmware version 32.011 and later · +2 more

Full record on NVD

Fix

  1. Mitigation from the vendor CISA ICSA-22-342-03 · 5 products32.016 and later for versions 32
  2. Mitigation from the vendor CISA ICSA-22-342-03 · 5 products33.015 and later for versions 33
  3. Mitigation from the vendor CISA ICSA-22-342-03 · 5 products34.011 and later
  4. Mitigation from the vendor CISA ICSA-22-342-03 · 5 productsControlLogix/GuardLogix 5580
  5. Mitigation from the vendor CISA ICSA-22-342-03 · 5 productsCompactLogix 5380
  6. Mitigation from the vendor CISA ICSA-22-342-03 · 5 productsCompactLogix 5480

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CISA-ADPSSVC decisionnone2025-04-16
  • OpenCVESSVC decisionnone—
  • CNACVSS 3.18.6read 2026-10-23
  • NVDCVSS 3.17.5read 2026-10-23
  • CNAweakness (CWE)CWE-20read 2026-10-23
  • FIRST EPSSEPSS score1.3 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Published
2022-12-19
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2022-3752?

An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation.

Is CVE-2022-3752 actively exploited?

Active exploitation of CVE-2022-3752 has not been confirmed. Its EPSS score was 1.3% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2022-3752?

CVE-2022-3752 has a CVSS v3 base score of 7.5 (HIGH severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.

Running Rockwell Automation Logix? Hear about its next vulnerability

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month