Skip to main content
ExploitedIn CISA KEV

CVE-2021-22681

Exploitation confirmed. First attested on 2026-03-05 by CISA-ADP, CISA KEV, GCVE · kevintel.

  • Published2021-03-03
  • WeaknessCWE-522

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

Timeline

dates in UTC
  1. 2021-03-0318:15CVE publishedNVD
  2. 2026-03-05Listed as exploited by GCVEGCVE
  3. 2026-03-05Exploitation first reportedCISA KEV
  4. 2026-03-05Added to the CISA KEV catalogCISA KEV
  5. 2026-03-0519:14SSVC exploitation set to activeCISA-ADP
  6. 2026-10-2319:23First public proof of conceptPoC-in-GitHub
  7. 2026-10-2319:23EPSS crossed 10 %FIRST EPSS

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2021-22681?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2021-22681?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Rockwellautomation factorytalk services platformversion to verify
BranchAffectedFixed in
2.10+≥ 2.10no fix published
Rockwellautomation rslogix 5000version to verify
BranchAffectedFixed in
20.x≥ 16, ≤ 20no fix published
Rockwellautomation studio 5000 logix designerversion to verify
BranchAffectedFixed in
21.0+≥ 21.0no fix published

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-21-056-03 CISA3 known affected

    Rockwell Automation Logix Controllers (Update A)

    RSLogix 5000: Versions 16 through 20 · Studio 5000 Logix Designer: Versions 21 and later · FactoryTalk Security part of the FactoryTalk Services Platform if configured and deployed: v2.10 and later

Full record on NVD

Fix

  1. CISA’s required action: Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.due 2026-03-26
  2. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsRockwell Automation has determined this vulnerability cannot be mitigated with a patch. Rockwell encourages users to combine its specific risk mitigation recommendations with general security guidelines for a comprehensive defense-in-depth strategy.
  3. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsA comprehensive defense-in-depth strategy can reduce the risk of this vulnerability. To reduce risk, Rockwell recommends users ensure they are employing proper network segmentation and security controls
  4. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsMinimizing network exposure for all control system devices and/or systems and confirm these devices are not accessible from the Internet.
  5. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsLocating control system networks and devices behind firewalls and isolating them from the enterprise/business network.
  6. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsRestricting or blocking traffic on TCP 44818 from outside of the industrial control system network zone. For more information on the TCP/UDP ports used by Rockwell Automation products, see BF7490 (login required).
  7. Mitigation from the vendor CISA ICSA-21-056-03 · 3 productsWhen remote access is required, use secure methods such as virtual private networks (VPNs), recognizing VPNs may have vulnerabilities and should be updated to the most current version available. VPN is only as secure as the connected devices.

Detection

read 2026-10-23 19:23 UTC
Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
1 repository, unverifiedpcrosby-1990/cip-security-poc
PoC-in-GitHub

CISA Known Exploited Vulnerability

Date Added
2026-03-05
Patch Due Date
2026-03-26
Ransomware Use
Unknown
Required Action
Apply mitigations per vendor instructions, follow applicable BOD 22-01 guidance for cloud services, or discontinue use of the product if mitigations are unavailable.

Sources

  • CISA KEVKEV entry2026-03-05
  • GCVEexploitation2026-03-05
  • CISA-ADPSSVC decisionactive2026-03-05
  • OpenCVESSVC decisionactive—
  • CISA-ADPCVSS 3.19.82026-03-05
  • NVDCVSS 3.19.8read 2026-10-23
  • NVDCVSS 2.07.5read 2026-10-23
  • CNAweakness (CWE)CWE-522read 2026-10-23
  • NVDweakness (CWE)CWE-522read 2026-10-23
  • FIRST EPSSEPSS score63.6 %read 2026-10-23
  • PoC-in-GitHubproof of concept1read 2026-10-23

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Published
2021-03-03
Last Modified
2026-06-17
NVD status
Analyzed

Frequently asked questions

What is CVE-2021-22681?

Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800.

Is CVE-2021-22681 actively exploited?

Yes. CVE-2021-22681 is on the CISA Known Exploited Vulnerabilities (KEV) catalog, meaning it has been confirmed as actively exploited in the wild. CISA requires federal agencies to patch by 2026-03-26.

What is the CVSS score for CVE-2021-22681?

CVE-2021-22681 has a CVSS v3 base score of 9.8 (CRITICAL severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.

Hear about the next vulnerability in your software

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month