Skip to main content
No exploitation reported

CVE-2020-8477

No exploitation reported by the sources we read.

  • Published2020-04-22
  • WeaknessCWE-489 · CWE-79

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

The installations for ABB System 800xA Information Manager versions 5.1, 6.0 to 6.0.3.2 and 6.1 wrongly contain an auxiliary component. An attacker is able to use this for an XSS-like attack to an authenticated local user, which might lead to execution of arbitrary code.

Timeline

dates in UTC
  1. 2020-04-2215:15CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2020-8477?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2020-8477?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Abb 800xa information manager
BranchAffectedFixed in
6.0≥ 6.0.0, ≤ 6.0.3.2no fix published
5.1= 5.1no fix published
6.1= 6.1no fix published

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-20-184-02 CISA3 known affected

    ABB System 800xA Information Manager

    System 800xA Information Manager: Versions prior to 6.0.3.3 RU1 · System 800xA Information Manager: Versions prior to 5.1 Rev E/5.1 FP4 Rev E TC6 · System 800xA Information Manager: Versions prior to 6.1 RU1

Full record on NVD

Fix

  1. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsThis vulnerability was corrected in System 800xA of the following versions: 5.1 Rev E/5.1 FP4 E TC6, ABB recommends users on the 5.1 track to install this TC, which can be obtained from technical support upon request.
  2. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsThis vulnerability was corrected in System 800xA of the following versions: 6.0.3.3 RU1, ABB recommends users on the 6.0.3 LTS track to update 6.0.3.3 and install RU1 for IM.
  3. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsThis vulnerability was corrected in System 800xA of the following versions: 6.1 RU1, ABB recommends users on the 6.1 track to update to this version.
  4. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsThe above-mentioned updates are recommended regardless of whether the previously described manual removal of the vulnerable component has been done or not. The IM rollups for 6.0.3.3 and 6.1 can be downloaded from My ABB/My Control System.
  5. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsPlease note this vulnerability can be exploited by remote and unauthenticated users, so users are recommended to ensure only authorized persons have access to plant assets and network and that web browsing from system nodes to external networks is restricted, especially from an IM node.
  6. Mitigation from the vendor CISA ICSA-20-184-02 · 3 productsCheck that the usage of the Access Enable key in AC 800M HI and the configured access level of SIL variables corresponds to the risk analysis.

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CNACVSS 3.18.8read 2026-10-23
  • NVDCVSS 3.18.8read 2026-10-23
  • NVDCVSS 2.06.8read 2026-10-23
  • CNAweakness (CWE)CWE-489, CWE-79read 2026-10-23
  • NVDweakness (CWE)CWE-79read 2026-10-23
  • FIRST EPSSEPSS score1.7 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H
Published
2020-04-22
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2020-8477?

The installations for ABB System 800xA Information Manager versions 5.1, 6.0 to 6.0.3.2 and 6.1 wrongly contain an auxiliary component. An attacker is able to use this for an XSS-like attack to an authenticated local user, which might lead to execution of arbitrary code.

Is CVE-2020-8477 actively exploited?

Active exploitation of CVE-2020-8477 has not been confirmed. Its EPSS score was 1.7% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2020-8477?

CVE-2020-8477 has a CVSS v3 base score of 8.8 (HIGH severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H.

Running ABB System 800xA Information? Hear about its next vulnerability

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month