CVE-2019-7225

No exploitation reported by the sources we read.

  • Published2019-06-27
  • WeaknessCWE-798

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.

Timeline

dates in UTC
  1. 2019-06-2717:15CVE publishedNVD

Versions per branch

NVD
Abb cp620 firmwareversion to verify
BranchAffectedFixed in
1.76≤ 1.76no fix published
Abb cp620-web firmwareversion to verify
BranchAffectedFixed in
1.76≤ 1.76no fix published
Abb cp630 firmwareversion to verify
BranchAffectedFixed in
1.76≤ 1.76no fix published

13 more products in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-19-178-01 CISA1 known affected

    ABB PB610 Panel Builder 600

    PB610 Panel Builder 600 order code: 1SAP500900R0101 Versions 1.91 … 2.8.0.367 and prior

  • ICSA-19-178-03 CISA9 known affected

    ABB CP635 HMI

    CP620-WEB order code: 1SAP520200R0001 revision index G1 with BSP UN31 v1.76 and prior · CP620 order code: 1SAP520100R0001 revision index G1 with BSP UN31 v1.76 and prior · CP630 order code: 1SAP530100R0001 revision index G1 with BSP UN31 v1.76 and prior · +6 more

Full record on NVD

Fix

  1. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productPB610 Panel Builder 600: v2.8.0.424.
  2. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productNew version of BSP (board support package) UN31: v2.31.
  3. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productNew version of BSP (board support package) UN30: v2.31.
  4. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productABB recommends users apply the update of the PB610 applications on CP600 control panels at the earliest convenience.
  5. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productIf an update of the devices is not possible. ABB recommends users restrict network access to the devices to only trusted parties/devices.
  6. Mitigation from the vendor CISA ICSA-19-178-01 · 1 productTo prevent an unauthorized login via a remote client, leave the “Force Remote Login” option of the security settings checked (default setting). In addition, set new users and passwords in the user's settings for remote clients to “use different user and password.”

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof of concept
Metasploit modules
none listed
Metasploit Framework

Sources

Identifiers

Technical details

CVSS v3 Vector
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
Published
2019-06-27
Last Modified
2026-06-17
NVD status
Modified
GitHub Advisory
GHSA-qh2p-23vc-r8qp

Frequently asked questions

What is CVE-2019-7225?

The ABB HMI components implement hidden administrative accounts that are used during the provisioning phase of the HMI interface. These credentials allow the provisioning tool "Panel Builder 600" to flash a new interface and Tags (MODBUS coils) mapping to the HMI. These credentials are the idal123 password for the IdalMaster account, and the exor password for the exor account. These credentials are used over both HTTP(S) and FTP. There is no option to disable or change these undocumented credentials. An attacker can use these credentials to login to ABB HMI to read/write HMI configuration files and also to reset the device. This affects ABB CP635 HMI, CP600 HMIClient, Panel Builder 600, IDAL FTP server, IDAL HTTP server, and multiple other HMI components.

Is CVE-2019-7225 actively exploited?

Active exploitation of CVE-2019-7225 has not been confirmed. Its EPSS score was 2.9% on 2026-11-08, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2019-7225?

CVE-2019-7225 has a CVSS v3 base score of 8.8 (HIGH severity), with vector string CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H.