CVE-2019-6575
No exploitation reported by the sources we read.
- Published2019-04-17
- Fixed in15.1
- WeaknessCWE-248 · CWE-755
Am I affected?
Debian, Ubuntu or Red Hat sometimes backport a fix without changing the upstream version number: such a version reads « to verify », never « affected ».With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.
Description
A vulnerability has been identified in SIMATIC CP 443-1 OPC UA (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions < V2.7), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants) (All versions < V15.1 Upd 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15.1 Upd 4), SIMATIC IPC DiagMonitor (All versions < V5.1.3), SIMATIC NET PC Software V13 (All versions), SIMATIC NET PC Software V14 (All versions < V14 SP1 Update 14), SIMATIC NET PC Software V15 (All versions), SIMATIC RF188C (All versions < V1.1.0), SIMATIC RF600R family (All versions < V3.2.1), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.5 < V2.6.1), SIMATIC S7-1500 Software Controller (All versions between V2.5 (including) and V2.7 (excluding)), SIMATIC WinCC OA (All versions < V3.15 P018), SIMATIC WinCC Runtime Advanced (All versions < V15.1 Upd 4), SINEC NMS (All versions < V1.0 SP1), SINEMA Server (All versions < V14 SP2), SINUMERIK OPC UA Server (All versions < V2.1), TeleControl Server Basic (All versions < V3.1.1). Specially crafted network packets sent to affected devices on port 4840/tcp could allow an unauthenticated remote attacker to cause a denial of service condition of the OPC communication or crash the device. The security vulnerability could be exploited by an attacker with network access to the affected systems. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise availability of the OPC communication.
Timeline
dates in UTC- 2019-04-1714:29CVE publishedNVD
Observed activity
isMalicious corpus · updated 2026-10-23 21:37 UTCBlock these indicators
- Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2019-6575?format=txt
- CSV export: https://api.ismalicious.com/edl/cve/CVE-2019-6575?format=csv
- TAXII collection of exploited CVEs
- The EDL and CSV take an API key on the Pro plan.
Versions per branch
NVD| Branch | Affected | Fixed in | Source |
|---|---|---|---|
| 15.1 | < 15.1 | 15.1 | NVD |
| 15.1 | = 15.1 | no fix published | NVD |
| Branch | Affected | Fixed in | Source |
|---|---|---|---|
| 15.1 | < 15.1 | 15.1 | NVD |
| 15.1 | = 15.1 | no fix published | NVD |
| Branch | Affected | Fixed in | Source |
|---|---|---|---|
| 15.1 | < 15.1 | 15.1 | NVD |
| 15.1 | = 15.1 | no fix published | NVD |
24 more products in the sources.
as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.
Distribution builds and vendor advisories
Packages from OSV.dev and products from the vendors' CSAF advisories.
version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.
Vendor advisories
Siemens Industrial Products with OPC UA (Update H)
SIMATIC CP 443-1 OPC UA · SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) · SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) · +16 more
Siemens SIMATIC Panels and WinCC (TIA Portal)
SIMATIC CP 443-1 OPC UA · SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) · SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants) · +16 more
Fix
- Update Siemens simatic hmi comfort outdoor panels firmware to 15.1
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V3.15 P018 or later version
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V14 SP2 or later version
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V1.0 SP1 or later version
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V2.7 or later version
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V2.1 or later version
- Vendor fix CISA ICSA-19-099-03 · 1 productUpdate to V3.1.1 or later version
Advisories and patches
- cert-portal.siemens.comVendor Advisory
Detection
- Nuclei template
- none so far ProjectDiscovery
- Exploit-DB
- no entry Exploit-DB
- Proof-of-concept repositories
- none listed PoC-in-GitHub
Sources
Technical details
- CVSS v3 Vector
- CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
- Published
- 2019-04-17
- Last Modified
- 2026-06-17
- NVD status
- Modified
Frequently asked questions
What is CVE-2019-6575?
Is CVE-2019-6575 actively exploited?
What is the CVSS score for CVE-2019-6575?
Running SIMATIC CP? Hear about its next vulnerability
Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».
No credit card required · No monthly cap on website lookups · 250 API requests/month
Go further
- Following what attackers exploit right now? The CISA KEV additions of the month, with their patch deadlines.
- Running this software? Vulnerability monitoring alerts you to new vulnerabilities in your products.
Related vulnerabilities
Same product first, then the same vendor advisory and the same publication week.