Debian, Ubuntu or Red Hat sometimes backport a fix without changing the upstream version number: such a version reads « to verify », never « affected ».With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.
Description
In Schneider Electric Triconex Tricon MP model 3008 firmware versions 10.0-10.4, system calls read directly from memory addresses within the control program area without any verification. Manipulating this data could allow attacker data to be copied anywhere within memory.
Timeline
dates in UTC- 2018-05-0417:29CVE publishedNVD
Versions per branch
NVD| Branch | Affected | Fixed in | Source |
|---|---|---|---|
| 10.x | ≥ 10.0, ≤ 10.4 | no fix published | NVD |
as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.
Distribution builds and vendor advisories
Packages from OSV.dev and products from the vendors' CSAF advisories.
version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.
Vendor advisories
Schneider Electric Triconex Tricon
MP Model 3008: >= 10.0 | <= 10.4
Fix
- Vendor fix CISA ICSA-18-107-02 · 1 productSchneider Electric strongly recommends that users upgrade to the latest Triconex Tricon CX version. Tricon CX v11.4 is now available and is compliant with the IEC 62443 cybersecurity standard and includes multiple security enhancements that meet the challenges posed by HatMan malware techniques and…
- Mitigation from the vendor CISA ICSA-18-107-02 · 1 productSchneider Electric has released the following security notification: https://www.schneider-electric.com/en/download/document/SEVD-2017-347-01/
- Mitigation from the vendor CISA ICSA-18-107-02 · 1 productDetect and Respond: Triconex users should contact their local Schneider Electric office for assistance. With this engagement, Schneider Electric will gather data from each Tricon safety system installation, analyze for the presence of the malware, and carry out any necessary malware removal procedu…
- Mitigation from the vendor CISA ICSA-18-107-02 · 1 productDetect and Respond: For users who choose to gather data from each Tricon safety system installation on their own, instructions and support material is available for download via the Schneider Electric Process Automation customer support portal (login required). The data will still need to be sent t…
- Mitigation from the vendor CISA ICSA-18-107-02 · 1 productDetect and Respond: Once Schneider Electric has analyzed this data, Triconex users will receive a report for each Tricon system analyzed. This report will advise whether the malware was detected, and what the next steps are to remove the malware if detected.A YARA rule that matches the binary compo…
- Mitigation from the vendor CISA ICSA-18-107-02 · 1 productDefend: The HatMan malware requires unrestricted access to the safety network via remote network or physical access. Additionally, the malware requires the Tricon key switch to be in the "PROGRAM" mode to successfully deploy its payload.
Advisories and patches
- www.schneider-electric.comVendor Advisory
Detection
- Nuclei template
- none so far ProjectDiscovery
- Exploit-DB
- no entry Exploit-DB
- Proof of concept
- PoC-in-GitHubno public repository identifiedread 2026-11-10
- Metasploit modules
- none listed Metasploit Framework
Sources
- NVDCVSS 3.08.1read 2026-10-23
- NVDCVSS 2.09.3read 2026-10-23
- CNAweakness (CWE)CWE-119known since 2026-10-23
- NVDweakness (CWE)CWE-119read 2026-10-23
- FIRST EPSSEPSS score2.2 %2026-11-09
- GitHub Advisoriesadvisory—
Identifiers
- EUVD-2018-20480same flawENISA EUVD · LicenseRef-ENISA-legal-notice
- GHSA-ggm5-5h63-2mvrsame flawGitHub Advisory Database · CC-BY-4.0
Technical details
- CVSS v3 Vector
- CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:H/I:H/A:H
- Published
- 2018-05-04
- Last Modified
- 2026-06-17
- NVD status
- Modified
- GitHub Advisory
- GHSA-ggm5-5h63-2mvr
Frequently asked questions
What is CVE-2018-8872?
Is CVE-2018-8872 actively exploited?
What is the CVSS score for CVE-2018-8872?
Running Schneider Electric Triconex? Hear about its next vulnerability
Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».
No credit card required · No monthly cap on website lookups · 250 API requests/month
Go further
- Following what attackers exploit right now? The CISA KEV additions of the month, with their patch deadlines.
- Running this software? Vulnerability monitoring alerts you to new vulnerabilities in your products.
Related vulnerabilities
Same product first, then the same vendor advisory and the same publication week.
Sources for this record
- CISA ICS advisories (CSAF) · Public domain (US Government work)
- CVE Program · CVE Program Terms of Use
- ENISA EU Vulnerability Database · ENISA legal notice §1.2 (reproduction authorised, provided the source is acknowledged)
- FIRST EPSS · EPSS terms of use (free use, attribution requested)
- GitHub Advisory Database · CC-BY-4.0 · GHSA-ggm5-5h63-2mvr
- NVD · Public domain (17 U.S.C. § 105) for NVD-authored data; third-party content under its own terms