Skip to main content
No exploitation reportedFix available

CVE-2018-16557

No exploitation reported by the sources we read.

  • Published2018-12-13
  • Fixed in6.0.9
  • WeaknessCWE-347

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Timeline

dates in UTC
  1. 2018-12-1316:29CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 21:37 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2018-16557?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2018-16557?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Siemens simatic s7-400h firmwareversion to verify
BranchAffectedFixed in
6.0≥ 6.0.0, < 6.0.96.0.9
4.5≤ v4.5no fix published
Siemens simatic s7-400 firmwareversion to verify
BranchAffectedFixed in
6.0≤ v6.0no fix published
Siemens simatic s7-400 pn\/dp v7 firmwareversion to verify
BranchAffectedFixed in
—all versionsno fix published

1 more product in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-18-317-02 CISA21 known affected

    Siemens S7-400 CPUs (Update B)

    SIMATIC S7-400 CPU 412-1 DP V7 (6ES7412-1XJ07-0AB0) · SIMATIC S7-400 CPU 412-2 DP V7 (6ES7412-2XK07-0AB0) · SIMATIC S7-400 CPU 414-2 DP V7 (6ES7414-2XL07-0AB0) · +18 more

Full record on NVD

Fix

  1. Update Siemens simatic s7-400h firmware to 6.0.9
  2. Vendor fix CISA ICSA-18-317-02 · 7 productsUpdate to V7.0.3 or later version
  3. Vendor fix CISA ICSA-18-317-02 · 1 productUpdate to V6.0.9 or later version
  4. Vendor fix CISA ICSA-18-317-02 · 1 productUpdate to V8.2.1 or later version
  5. Mitigation from the vendor CISA ICSA-18-317-02 · 21 productsCVE-2018-16557: Configure protection level 3 (read/write protection)
  6. Mitigation from the vendor CISA ICSA-18-317-02 · 21 productsRestrict network access to affected devices; restrict network access to port 102/tcp for Ethernet interfaces
  7. Mitigation from the vendor CISA ICSA-18-317-02 · 1 productActivate Field Interface Security in PCS 7 V9.0, and use a SIMATIC/SIPLUS CP443-1 Adv. to communicate with ES/OS

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CNACVSS 3.18.2read 2026-10-23
  • NVDCVSS 3.17.5read 2026-10-23
  • NVDCVSS 2.07.8read 2026-10-23
  • CNAweakness (CWE)CWE-347read 2026-10-23
  • FIRST EPSSEPSS score0.8 %2026-10-23

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Published
2018-12-13
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2018-16557?

A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Sending of specially crafted packets to port 102/tcp via Ethernet interface via PROFIBUS or Multi Point Interfaces (MPI) could cause a denial of service condition on affected devices. Flashing with a firmware image may be required to recover the CPU. Successful exploitation requires an attacker to have network access to port 102/tcp via Ethernet interface or to be able to send messages via PROFIBUS or Multi Point Interfaces (MPI) to the device. No user interaction is required. If no access protection is configured, no privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

Is CVE-2018-16557 actively exploited?

Active exploitation of CVE-2018-16557 has not been confirmed. Its EPSS score was 0.8% on 2026-10-23, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2018-16557?

CVE-2018-16557 has a CVSS v3 base score of 7.5 (HIGH severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H.

Running SIMATIC S7-400 CPU? Hear about its next vulnerability

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month