Skip to main content
No exploitation reportedFix available

CVE-2018-13812

No exploitation reported by the sources we read.

  • Published2018-12-13
  • WeaknessCWE-22

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). A directory traversal vulnerability could allow to download arbitrary files from the device. The security vulnerability could be exploited by an attacker with network access to the integrated web server. No user interaction and no authentication is required to exploit the vulnerability. The vulnerability impacts the confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Timeline

dates in UTC
  1. 2018-12-1316:29CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2018-13812?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2018-13812?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Siemens simatic hmi comfort outdoor panels firmwareversion to verify
BranchAffectedFixed in
15.0≤ 15.0no fix published
Siemens simatic hmi comfort panels firmwareversion to verify
BranchAffectedFixed in
15.0≤ 15.0no fix published
Siemens simatic hmi ktp mobile panels ktp400f firmwareversion to verify
BranchAffectedFixed in
15.0≤ 15.0no fix published

9 more products in the sources.

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-18-317-08 CISA7 known affected

    Siemens SIMATIC Panels

    Siemens SIMATIC HMI Comfort Panels 4" - 22" (incl. SIPLUS variants): All versions < V15 Update 4 · Siemens SIMATIC HMI Comfort Outdoor Panels 7" & 15" (incl. SIPLUS variants): All versions < V15 Update 4 · Siemens SIMATIC HMI KTP Mobile Panels KTP400F KTP700 · +4 more

Full record on NVD

Fix

  1. Vendor fix CISA ICSA-18-317-08 · 3 productsUpdate SIMATIC WinCC (TIA Portal) to V15 Update 4 or newer, and then update panel to V15 Update 4 or newer. https://support.industry.siemens.com/cs/ww/en/view/109755826
  2. Vendor fix CISA ICSA-18-317-08 · 3 productsUpdate to V15 Update 4 or newer https://support.industry.siemens.com/cs/ww/en/view/109755826
  3. Mitigation from the vendor CISA ICSA-18-317-08 · 7 productsRestrict network access to the integrated web server.
  4. Mitigation from the vendor CISA ICSA-18-317-08 · 7 productsDeactivate the web server if not required. The web server is disabled by default.

Advisories and patches

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • NVDCVSS 3.07.5read 2026-10-23
  • NVDCVSS 2.05read 2026-10-23
  • CNAweakness (CWE)CWE-22read 2026-10-23
  • NVDweakness (CWE)CWE-22read 2026-10-23
  • FIRST EPSSEPSS score3.6 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
Published
2018-12-13
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2018-13812?

A vulnerability has been identified in SIMATIC HMI Comfort Panels 4" - 22" (All versions < V15 Update 4), SIMATIC HMI Comfort Outdoor Panels 7" & 15" (All versions < V15 Update 4), SIMATIC HMI KTP Mobile Panels KTP400F, KTP700, KTP700F, KTP900 and KTP900F (All versions < V15 Update 4), SIMATIC WinCC Runtime Advanced (All versions < V15 Update 4), SIMATIC WinCC Runtime Professional (All versions < V15 Update 4), SIMATIC WinCC (TIA Portal) (All versions < V15 Update 4), SIMATIC HMI Classic Devices (TP/MP/OP/MP Mobile Panel) (All versions). A directory traversal vulnerability could allow to download arbitrary files from the device. The security vulnerability could be exploited by an attacker with network access to the integrated web server. No user interaction and no authentication is required to exploit the vulnerability. The vulnerability impacts the confidentiality of the device. At the time of advisory publication no public exploitation of this security vulnerability was known.

Is CVE-2018-13812 actively exploited?

Active exploitation of CVE-2018-13812 has not been confirmed. Its EPSS score was 3.6% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2018-13812?

CVE-2018-13812 has a CVSS v3 base score of 7.5 (HIGH severity), with vector string CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N.

Running SIMATIC HMI Comfort Panels? Hear about its next vulnerability

Surveillance reads the versions in your stack — a domain, a lockfile or a list — checks each CVE against the ranges its sources publish, and alerts you when one you run is exploited or enters CISA KEV. A version it cannot read stays « version not verified ».

No credit card required · No monthly cap on website lookups · 250 API requests/month