Skip to main content
No exploitation reported

CVE-2017-6030

No exploitation reported by the sources we read.

  • Published2017-06-30
  • WeaknessCWE-331 · CWE-343

Am I affected?

With a domain, we read the version its public headers and pages expose. A distribution build can carry the fix under an older number.

Description

A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.

Timeline

dates in UTC
  1. 2017-06-3003:29CVE publishedNVD

Observed activity

isMalicious corpus · updated 2026-10-23 18:48 UTC
Indicators tagged with this CVE, per day0 indicators over 7 days
Block these indicators
  • Firewall list (EDL, text): https://api.ismalicious.com/edl/cve/CVE-2017-6030?format=txt
  • CSV export: https://api.ismalicious.com/edl/cve/CVE-2017-6030?format=csv
  • TAXII collection of exploited CVEs
  • The EDL and CSV take an API key on the Pro plan.

Versions per branch

NVD
Schneider-electric modicon m221 firmwareversion to verify
BranchAffectedFixed in
1.1≤ 1.1.1.5no fix published
Schneider-electric modicon m241 firmwareversion to verify
BranchAffectedFixed in
4.0≤ 4.0.3.20no fix published
Schneider-electric modicon m251 firmwareversion to verify
BranchAffectedFixed in
4.0≤ 4.0.3.20no fix published

as publishedRanges as NVD and OSV publish them; a distribution’s build can be fixed under an older number.

Distribution builds and vendor advisories

Packages from OSV.dev and products from the vendors' CSAF advisories.

version not verifiedVersions not verified: read as OSV.dev and the vendors publish them, not checked against each vendor's release list.

Vendor advisories

  • ICSA-17-089-02 CISA5 known affected

    Schneider Electric Modicon PLCs

    Modicon M221: firmware versions prior to Version 1.5.0.0 · Modicon M241: firmware versions prior to Version 4.0.5.11 · Modicon M251: all versions · +2 more

Full record on NVD

Fix

  1. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsSchneider Electric has released new firmware versions to address the predictable value range from previous values vulnerability and the use of insufficiently random values vulnerability, which are available through Schneider Electric's software update tool, SoMachine, Version 4.2, and SoMachineBasi…
  2. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsSoMachineBasic, Version 1.5, is available
  3. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsVerify that the hardware and software infrastructure that the PLCs are integrated into (along with all organizational measures and rules covering access to the infrastructure) consider the results of the hazard and risk analysis, and are implemented according to best practices and standards such as…
  4. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsLimit traffic on the local network with managed switches
  5. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsWhere possible, avoid using Wi-Fi networks, but when Wi-Fi is essential, use only secure communications (such as WPA2 encryption)
  6. Mitigation from the vendor CISA ICSA-17-089-02 · 5 productsDo not grant [network] access to unknown computers

Detection

Nuclei template
none so far
ProjectDiscovery
Exploit-DB
no entry
Exploit-DB
Proof-of-concept repositories
none listed
PoC-in-GitHub

Sources

  • CISA-ADPSSVC decisionnone2026-05-29
  • OpenCVESSVC decisionnone—
  • CISA-ADPCVSS 3.16.52026-05-29
  • NVDCVSS 3.16.5read 2026-10-23
  • NVDCVSS 2.06.4read 2026-10-23
  • CNAweakness (CWE)CWE-343read 2026-10-23
  • NVDweakness (CWE)CWE-331read 2026-10-23
  • FIRST EPSSEPSS score2.1 %2026-10-22

Technical details

CVSS v3 Vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L
Published
2017-06-30
Last Modified
2026-06-17
NVD status
Modified

Frequently asked questions

What is CVE-2017-6030?

A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate insufficiently random TCP initial sequence numbers that may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections.

Is CVE-2017-6030 actively exploited?

Active exploitation of CVE-2017-6030 has not been confirmed. Its EPSS score was 2.1% on 2026-10-22, the estimated probability of exploitation in the next 30 days.

What is the CVSS score for CVE-2017-6030?

CVE-2017-6030 has a CVSS v3 base score of 6.5 (MEDIUM severity), with vector string CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:L/A:L.